Displaying 1 publication

Abstract:
Sort:
  1. Nor Mohd Razif Noraini, Leman, A.M., Ahmad Sayuti ZainalAbidin, Ruslina Mohd. Jazar, LailaShuhada Mat Zin, Rasdan Ismail, et al.
    MyJurnal
    This study has been conducted in a new constructed building of NIOSH Malaysia located at Bandar Baru Bangi, Selangor. The goal of the case study is focusing on the level of Indoor Air Contaminants (IAC) including chemical contaminants within three consequent stages which are before furniture install, after furniture install and during one month occupancy. This study was divided the sampling area into two main facilities which are training and office setting. The contaminants has been measured consist of sixparameters such as Carbon Dioxide (CO2), Carbon Monoxide (CO), Total Volatile Organic Compounds (TVOC), Formaldehyde, Respirable Particulates (PM10) and Ozone. The result of Carbon Monoxide (CO), Total Volatile Organic Compound (TVOC), Respirable Particulates (PM10) and Ozone show an increasing trend across the three sampling stages. The Formaldehyde show an increasing trend in the first and second stages but were reduced significantly the last stage of sampling. These finding indicates that furniture and fittings installed might be a potential sources of indoor air contaminants. The management should be aware to their indoor air status to protect the occupant from the risk of unwanted exposure especially during the early stage of building occupancy.
Related Terms
Filters
Contact Us

Please provide feedback to Administrator (afdal@afpm.org.my)

External Links