ISA Trans, 2010 Oct;49(4):559-66.
PMID: 20667537 DOI: 10.1016/j.isatra.2010.06.007

Abstract

The performance of a chemical process plant can gradually degrade due to deterioration of the process equipment and unpermitted deviation of the characteristic variables of the system. Hence, advanced supervision is required for early detection, isolation and correction of abnormal conditions. This work presents the use of an adaptive neuro-fuzzy inference system (ANFIS) for online fault diagnosis of a gas-phase polypropylene production process with emphasis on fast and accurate diagnosis, multiple fault identification and adaptability. The most influential inputs are selected from the raw measured data sets and fed to multiple ANFIS classifiers to identify faults occurring in the process, eliminating the requirement of a detailed process model. Simulation results illustrated that the proposed method effectively diagnosed different fault types and severities, and that it has a better performance compared to a conventional multivariate statistical approach based on principal component analysis (PCA). The proposed method is shown to be simple to apply, robust to measurement noise and able to rapidly discriminate between multiple faults occurring simultaneously. This method is applicable for plant-wide monitoring and can serve as an early warning system to identify process upsets that could threaten the process operation ahead of time.