Top-Oil Temperature (TOT) is one of the basic components to estimate the Hot-Spot temperature (HST) of the transformers. This paper presents an alternative TOT model based on the heat transfer theory that utilises Nonlinear Thermal Resistance (NTR) and Lumped Capacitance (LC) approaches. It is applied in a thermal-electrical analogy and the heat transfer equivalent equation is determined. This model is tested on a measured TOT of 250 MVA ONAF and 400 MVA ONAF transformers obtained from IEC 60076-7 and previous research. A comparison of TOT is carried out with the existing models IEC 60076-7 exponential and IEEE Loading Guide clause 7 methods. It is found that the thermal model based on the NTR and LC approach could determine the measured TOT closer than the existing methods available in the standards.
Transformer failures lead to interruption of power supply. Therefore, asset management is important to monitor the efficient functioning of transformers. An important approach in asset management is condition assessment whereby the health status of the transformer is assessed via a health index. There are many methods in determining the final value of a health index. This paper examines how different assessment methods can be used in order to come up with the final health index and output of final health index. The output trend shapes are almost the same for Assessment Model A, B and C except for Assessment Model D. There is no strong correlation between the health index and age of the transformer. Generally, the value of health index of the transformer is reflected by its operation and loading history .This paper hence examines the assessment steps and results that will guide the development of a new approach to determine health index value.
This paper presents an investigation on the physio-mechanical properties and AC breakdown voltage of the Kenaf paper in the presence of Polyvinyl Alcohol (PVA) for transformers application. Kenaf bast fibers were used in order to produce the paper through the soda pulping process. The pulps were subjected to beating up to 12,000 revolutions, whereby the PVA was added to the pulps at a different weight percentage concentration up to 12%. Morphological study was carried out on the Kenaf paper based on Scanning Electron Microscopy (SEM). The apparent density, Tensile Index (TI), Burst Index (BI), Tear Index (TeI), and AC breakdown voltage of the Kenaf paper were measured. It is found that the TI and BI of Kenaf paper can be slightly improved through the introduction of PVA. On other hand, the TeI of the Kenaf paper decreases with the increment of the PVA. The AC breakdown voltage of the Kenaf paper slightly increases with the increment of PVA weight percentage concentration.
This study presents an investigation on the effect of shield placement for mitigation of transient voltage in a 33/11 kV, 30 MVA transformer due to Standard Switching Impulse (SSI) and Oscillating Switching Impulse (OSI) surges. Generally, the winding and insulation in transformers could experience severe voltage stress due to the external impulses i.e. switching events. Hence, it is important to examine the voltage stress and identify the mitigation action i.e. shield placements in order to reduce the adverse effect to the transformer windings. First, the resistances, inductances, and capacitances (RLC) were calculated for disc type transformer in order to develop the winding RLC equivalent circuit. The SSI and OSI transient voltage waveforms were applied to the High Voltage (HV) winding whereby the transient voltages were simulated for each disc. The resulting voltage stresses were mitigated through different configurations of electrostatic shield placements. The resonant oscillations generated due to switching surges were analysed through initial voltage distribution. The analyses on the transient voltages of the transformer winding and standard error of the slope (SEb) reveal that the location of shield placement has a significant effect on the resonant switching voltages. The increment of the shield number in the windings does not guarantee optimize mitigation of the resonant switching transient voltages. It is found that the voltage stress along the windings is linear once a floating shield is placed between the HV and Low Voltage (LV) windings of the disc-type transformer under the SSI and OSI waveforms. These findings could assist the manufacturers with appropriate technical basis for mitigation of the transformer winding against the external transient switching overvoltage surges.
This experimental study aims to examine the partial discharge (PD) properties of palm oil and coconut oil (CO) based aluminum oxide (Al2O3) nanofluids with and without surfactants. The type of surfactant used in this study was sodium dodecyl sulfate (SDS). The volume concentrations range of Al2O3 dispersed in oil samples was varied from 0.001% to 0.05%. The ratio of surfactants to nanoparticles was set to 1:2. In total, two different types of refined, bleached and deodorized palm oil (RBDPO) and one type of CO were measured for PD. Mineral oil (MO) was also examined for comparison purpose. PDIV measurements for all samples were carried out based on rising voltage method whereby a needle-sphere electrode configuration with a gap distance of 50 mm was chosen in this study. Al2O3 improves the PDIVs of RBDPO, CO and MO whereby the highest improvements of PDIVs are 34%, 39.3% and 27%. The PD amplitude and repetition rate of RBDPO improve by 38% and 81% while for CO, it can increase up to 65% and 80% respectively. The improvement of PD amplitude and repetition rate for MO are 18% and 95%, regardless with and without SDS. Without SDS, the presence of Al2O3 could cause 26%, 75% and 65% reductions of the average emission of light signals for RBDPOA, RBDPOB and CO with the improvement of PD characteristics but both events do not correlate at the same volume concentration of Al2O3. On the other hand, the average emission of light signal levels of the oils increases with the introduction of SDS. The emission of light signal in MO does not correlate with the PD characteristics improvement either with or without SDS.
This paper proposes an alternative approach to extract transformer's winding parameters of resistance (R), inductance (L), capacitance (C) and conductance (G) based on Finite Element Method (FEM). The capacitance and conductance were computed based on Fast Multiple Method (FMM) and Method of Moment (MoM) through quasi-electrostatics approach. The AC resistances and inductances were computed based on MoM through quasi-magnetostatics approach. Maxwell's equations were used to compute the DC resistances and inductances. Based on the FEM computed parameters, the frequency response of the winding was obtained through the Bode plot function. The simulated frequency response by FEM model was compared with the simulated frequency response based on the Multi-conductor Transmission Line (MTL) model and the measured frequency response of a 33/11 kV, 30 MVA transformer. The statistical indices such as Root Mean Square Error (RMSE) and Absolute Sum of Logarithmic Error (ASLE) were used to analyze the performance of the proposed FEM model. It is found that the simulated frequency response by FEM model is quite close to measured frequency response at low and mid frequency regions as compared to simulated frequency response by MTL model based on RMSE and ASLE analysis.
Protection of medium voltage (MV) overhead lines against the indirect effects of lightning is an important issue in Malaysia and other tropical countries. Protection of these lines against the indirect effects of lightning is a major concern and can be improved by several ways. The choice of insulator to be used for instance, between the glass, ceramic or polymer, can help to improve the line performance from the perspective of increasing the breakdown strength. In this paper, the electrical performance of a 10 kV polymer insulator under different conditions for impulse, weather and insulator angle with respect to a cross-arm were studied (both experimental and modelling) and the results were discussed accordingly. Results show that the weather and insulator angle (with respect to the cross-arm) are surprisingly influenced the values of breakdown voltage and leakage current for both negative and positive impulses. Therefore, in order to select a proper protection system for MV lines against lightning induced voltage, consideration of the local information concerning the weather and also the insulator angles with respect to the cross-arm are very useful for line stability and performance.
This paper presents a sealed ageing study of palm oil (PO) and coconut oil (CO) in the presence of insulation paper. The type of PO under study is refined, bleached, and deodorized palm oil (RBDPO) olein. Three different variations of RBDPO and one sample of CO are aged at temperatures of 90 °C, 110 °C, and 130 °C. The properties of RBDPO and CO as well as paper under ageing are then analysed through dielectric and physicochemical measurements. It is found that the effect of ageing is not significant on the alternating current (AC) breakdown voltages and relative permittivities of RBDPO and CO. There is a slight increment trend of the resistivity for CO, while for all of the RBDPO, the resistivity slightly decreases as the ageing progresses. Only CO shows an apparent reduction of the dielectric dissipation factor. Throughout the ageing time, the acidities of all of the RBDPO and CO remain at low level, while the moisture in oils decreases. The tensile index (TI) of the papers for all of the RBDPO and CO retain more than 50% of the TI. A significant increment of the paper ageing rates of all of the RBDPO and CO is observed at an ageing temperature of 130 °C.
Located near the equator, Malaysia is a country with one of the highest lightning densities in the world. Lightning contributes to 70% of the power outages in Malaysia and affects power equipment, automated network systems, causes data losses and monetary losses in the nation. Therefore, consideration of insulator evaluation under lightning impulses can be crucial to evaluate and attempt to overcome this issue. This paper presents a new approach to increase the electrical performance of polymer insulators using a Room Temperature Vulcanisation (RTV) coating. The evaluation involves three different settings of polymer insulator, namely uncoated, RTV type 1, and RTV type 2 upper surface coatings. All the insulators were tested under three different conditions as dry, clean wet and salty under different impulse polarities using the even-rising test method. The voltage breakdown for each test was recorded. From the experiment, it was found that the effectiveness of the RTV coating application became apparent when tested under salty or polluted conditions. It increased the voltage withstand capabilities of the polymer insulator up to 50% from the basic uncoated insulator. Under dry and clean conditions, the RTV coating provided just a slight increase of the breakdown voltage. The increase in voltage breakdown capability decreased the probability of surface discharge and dry band arcing that could cause degradation of the polymeric material housing. The RTV type 1 coating was found to be more effective when performing under a lightning impulse. The findings might help the utility companies improve the performance of their insulators in order to increase power system reliability.
In this paper, the effect of different types of surfactants on the lightning breakdown voltages of palm oil (PO) and coconut oil (CO) based aluminium oxide (Al2O3) nanofluids is investigated. Three different types of surfactants were used in this study known as cationic (cetyl trimethyl ammonium bromide (CTAB)), anionic (sodium dodecyl sulfate (SDS)) and non-ionic (oleic acid (OA)). The volume percentage concentrations of Al2O3 dispersed into PO and CO were varied from 0.001% to 0.05%. The ratio of surfactant to the nanoparticles was set to 50% from the volume concentration of nanoparticles which equivalent to 1:2. In total, two types of refined, bleached and deodorized palm oil (RBDPO) and one type of CO were examined for lightning breakdown voltage. The test was carried out based on needle-sphere electrodes configuration with 25 mm gap distance. The presence of Al2O3 improves both positive and negative lightning breakdown voltages of RBDPO and CO. Under the positive and negative polarities, the CTAB does provide further improvements on the lightning breakdown voltages of RBDPOA (1st type of samples) and CO at most of the volume of concentration of Al2O3. SDS and OA could also further improve the lightning breakdown voltage of CO at certain volume concentration of Al2O3. On the other hand, the lightning breakdown voltage of RBDPOB based Al2O3 nanofluid (2nd type of samples) does not further improve with the introduction of surfactants. At most of the volume concentration of Al2O3, the introduction of CTAB further increases the times to breakdown and decrease the average streamer velocities of RBDPOA under both polarities. The same finding is observed for CO under positive polarity with CTAB and SDS as well as under negative polarity in the presence of all surfactants. The streamer velocities and times to breakdown patterns of RBDPOB based Al2O3 nanofluid are inconsistent in the presence of all surfactants. It is found that RBDPO and CO based Al2O3 nanofluids have second mode of streamer whereby the streamer velocities are from 1 km s-1 to 1.63 km s-1 regardless with or without surfactants.
The stimulant and toxicity effects of reported organic (acetic acid, propionic acid, butyric acid, formic acid, oil & grease) and inorganic (copper) by-products presented in palm oil mill effluent on anaerobic bacterial population were examined in this paper. The toxicity test had shown that acetic, propionic and butyric acids tend to stimulate the bacterial density level (survival rate more than 50%), while formic acid, copper, oil and grease were shown to have suppressed the density level (survival rate less than 50%). The highest biomass recorded was 1.66 mg/L for the concentration of acetic acid at 216 mg/L and lowest biomass concentration, 0.90 mg/L for copper at 1.40 mg/L. Biohydrogen-producing bacteria have a favourable growth rate around pH 5.5. The comparison of half maximal effective concentration (EC50) values between two test duration on the effects of organic and inorganic by-products postulate that bacteria had a higher tolerance towards volatile fatty acids. While acetic, butyric and propionic acids had exhibited higher tolerance EC50 values for bacteria, but the opposite trend was observed for formic acid, copper and oil & grease.
Sustainable materials, such as vegetable oils, have become an effective alternative for liquid dielectrics in power transformers. However, currently available vegetable oils for transformer application are extracted from edible products with a negative impact on food supply. So, it is proposed in this study to develop cottonseed oil (CSO) as an electrical insulating material and cooling medium in transformers. This development is performed in two stages. The first stage is to treat CSO with tertiary butylhydroquinone (TBHQ) antioxidants in order to enhance its oxidation stability. The second and most important stage is to use the promising graphene oxide (GO) nanosheets to enhance the dielectric and thermal properties of such oil through synthesizing GO-based CSO nanofluids. Sodium dodecyl sulfate (SDS) surfactant was used as surfactant for GO nanosheets. The nanofluid synthesis process followed the two-step method. Proper characterization of GO nanosheets and prepared nanofluids was performed using various techniques to validate the structure of GO nanosheets and their stability into the prepared nanofluids. The considered weight percentages of GO nanosheets into CSO are 0.01, 0.02, 0.03 and 0.05. Dielectric and thermal properties were comprehensively evaluated. Through these evaluations, the proper weight percentage of GO nanosheets was adopted and the corresponding physical mechanisms were discussed.