Affiliations 

  • 1 Universiti Kebangsaan Malaysia
MyJurnal

Abstract

Electricity has become one of the necessities for human daily activities. The presence of electric
current produces electromagnetic fields (EMF) at extremely low frequency (ELF). The problem arises
when scientists suggests a possible connection between ELF exposure to human health and safety.
Concerned about the safety and health of students and staff, Universiti Kebangsaan Malaysia (UKM)
took the initiative to identify possible ELF sources and measure their exposure in various locations
around the UKM main campus in Bangi. This paper reports the results obtained from the monitoring
of the magnetic flux density at three identified locations in the vicinity of the overhead high-voltage
transmission line which transverses the university compound and compare the maximum value results
with the exposure limit suggested by the International Committee on Non Ionising Radiation
Protection (ICNIRP) for ELF. Measurements were done with an (Extech) Three Axis
Electromagnetic Field (EMF) Meter (Model 430826) to determine the magnetic flux density. The
lateral profile method was applied as the standard measurement methodology. Results showed that the
maximum value of the magnetic flux density was 12.5 mG, which is below the suggested ICNIRP
public exposure limit of 1000 mG, or in percentage ratio, 1.25% of ICNIRP public exposure limit.
Results from the statistical Kruskal-Wallis test showed that there is a significant difference in the
distributions of the magnetic flux densities at the different locations (P < 0.05). In conclusion, the
measured locations are still safe for people in short-term exposure. However, long-term exposure
measurements still need to be done to provide concrete data on the ELF-emission levels in UKM.